CTec Compact Wall VAD c/w 91dB Sounder, Red 

£29.80 ex. VAT - £35.76 inc. VAT

SKU: BF451A/CX/SR Category:

Key Features:

  • Third-party certified to EN54-3 (Sounders), EN54-23 (VADs) and 17 (Isolators) by Intertek (pending)
  • Provides ‘W-2.4-3.5’ light distribution when wall mounted (min. 0.4 lux over a 2.4 x 3.5m cuboid area)
  • Can also provide ‘C-3-8 light distribution when ceiling mounted (min 0.4 lux over a 3 x 8m cylindrical area)
  • Impressive 90dB(A) sound output @ 1m
  • Unique C-TEC designed lens maximises light output whilst minimising current draw
  • Onboard short-circuit loop isolator
  • 550uA quiescent current
  • 14mA alarm current @24V DC (VAD lit, sounder on max)
  • Attractively finished in red polycarbonate (light output is white)
  • Group addressing facility allows multiple devices to be operated simultaneously
  • 7 selectable volume levels and up to 15 selectable tone pairs
  • Attractive compact design – just 102mm diameter, 63mm deep
  • Includes an integrated sounder to base locking mechanism
  • IP21C rated
  • Low current consumption means multiple devices can be connected to the loop
  • DIP switch addressed
  • Simple ‘click and twist’ design and easy-fit base ensures rapid installation time
  • Also available in a white plastic housing (order code BF451A/CX/SW)
Contact Us Via WhatsApp

10 in stock (can be backordered)

Quantity:

Our new BF451A/CX/SW Compact Addressable Wall VAD c/w 90dB(A) Sounder utilises the latest advances in sounder, LED and LED lens technology to provide a truly exceptional W-2.4-3.5 fire alarm warning device.

The Compact range of addressable, loop-powered, devices includes sounders, visual alarm devices (VADs) and combined sounder VADs. They are designed for indoor use with C-TEC’s ZFP/XFP and other Apollo Discovery compatible fire panels. Their purpose is to visually and audibly alert building occupants of a fire alarm.

The devices offer low current consumption, high sound output, ultra-bright white LEDs, 7 volume levels, 15 selectable tone pairs and built-in short-circuit loop isolators.

The sounder and VAD on the combined device can be set to operate independently of each other (panel dependent function). All devices are designed to comply with the relevant sections of the fire alarm device standards EN 54-3 (Sounders), EN 54-23 (Visual alarm devices – VADs) and EN 54-17 (Short-circuit isolators).

Other features include seven selectable volume levels, 15 tone pairs, a flash rate of 0.5Hz (once every two seconds) and a group addressing function to ensure the synchronised operation of multiple devices.

Attractively finished in white polycarbonate, the BF451A/CX/SR comes with an integrated sounder VAD/base locking mechanism and a plastic ID tag.

The BF451A/CX/SR can also be used to provide C-3-8 coverage when mounted on a ceiling.

 